Description

Product Description:

Diesel Generator Set

Engine Make /Model Perkins,2806A-E18TAG2
Alternator Make /Model Stamford, S5L1D-C4
Control Panel Stamford, S5L1D-F4
Base Frame / Silent Canopy N/A
Circuit Breaker Type 3 Pole MCCB
Battery Maintenance free Lead Acid

Dimensions Length  (mm) Width  (mm) Height  ( mm) Weight  (KG )
Close Type 5000 1900 2550 6000

Engine Specifications

Engine Make Model Perkins , 2806A-E18TAG2
No. of Cylinders 6 vertical in-line
Cycle 4 Stroke
Aspiraton Turbocharged and air-to-air chargecooled
Cooling Method N/A
Governing Type Electronic
Displacement 18.1 L
Bore/Stroke 145 x 183mm
Compression Ratio 14.5:1
Standby power 543kW
Prime power 598kW

Comply with Standards
GB/T 2820.1~6-2009 、 GB/T  2820.8~ 10-2002 、 GB/T  2820.12-2002 、 JB/T  10303-2001  JB/T  2819-1995 、 JB8587-1997 、 ISO8528 、 ISO3046

Alternator Specifications

Alternator Make /Model Stamford, S5L1D-F4
Number of Poles 4
Number of Winding Leads 12
Type of Bearing Single Bearing
Insulation Class -Temp Rise Cont. H -125/40 ℃
Ingress Protection Rating   IP 23
Excitaton System PMG
Voltage Regulation +/- 1%
Harmonic Coefcient THF < 2%
Tel. infuence TIF < 50
AVR Type N/A
Cooling Air Flow N/A
Maximum overspeed 2250rpm

For more detailed information on generator sets, please contact our professional business.